The MVHR fan control is based on the room relative humidity detected by the multisensors.
The multisensors with the highest relative humidity gets compared to the below parameters, depending which band it falls under the fan output speed will be set.
MVHR Modes (Activation):
Based on Relative Humidity (only). No user needs to be present for this to activate.
There is no Standby mode in this space.
Normal:
RH 0% - 39% = Low speed (pre-set by DAIKIN) & Auto mode (Heat exchange or Bypass mode via the VAM unit)
RH 40%-79% = High speed (pre-set by DAIKIN) & Auto mode (Heat exchange or Bypass mode via the VAM unit)
RH 80%-100% = High speed (pre-set by DAIKIN & Bypass mode